Did you know: Armstrong has 12 worldwide manufacturing facilities.

• Thermal Shutdown Mode
• +/- 2°F Temperature Stability to fixture
• Maximum Temperature Limit Stop
• Maximum Temperature Locking Feature
• Single “sealed for life” Replacement Cartridge

Thermostatic Mixing Valves

Thermostatic

Water Temperature Control - Single Point of Use - Thermostatic, features thermostatic mixing valves which are designed specifically for installation at or near the final point of use.

The range has been designed to offer accurate temperature control in installations where there are diverse flow requirements between .5 and 11 gpm (1.9 and 41.6 lpm).

Sizing

To size a mixing valve for single open outlet applications, simply match the required flow rate with the available maintained inlet water pressure. Correlate with required minimum flow rate and make a selection.

 Rada Thermostatic Mixing Valves (gpm)
Model Pressure Drip (psi) Min. Flow Cv
5 10 15 20 25 30 35 40 45 50
110 - .75 - 1.25 - 1.75 - 2.25 - 2.5 .5 .25
215 4 5 7 8 9 9 10 11 11 12 .5 1.7

For an application drawing on Thermostatic Mixing Valves, please click here.